4 core cu/xlpe/swa/pvc and 4 core al/xlpe/sct/pe Equivalent Cable Size Comparison
Nominal cross-sectional area
For CU
Cu conductor current rating (Amperes)
Votage drop CU conductor
(mV/A/m)
Votage drop AL conductor
(mV/A/m)
Equivalent current rating of AL conductor (Amperes)
Nominal cross-sectional area
For AL
10mm²
73
4.0
4.2
76
16mm²
16mm²
94
2.5
2.7
90
25mm²
25mm²
124
1.65
1.45
136
50mm²
35mm²
154
1.15
0.97
174
70mm²
50mm²
187
0.87
0.72
211
95mm²
70mm²
238
0.60
0.58
245
120mm²
95mm²
289
0.45
0.47
283
150mm²
120mm²
335
0.37
0.39
323
185mm²
150mm²
386
0.30
0.31
382
240mm²
185mm²
441
0.26
0.26
440
300mm²
240mm²
520
0.21
0.22
517
400mm²
300mm²
599
0.185
0.19
605
500mm²
400mm²
673
0.165
0.175
691
630mm²
The continous current carrying capacities are based on the following condition :
(i) Ambient temp 30°C
(ii) Max. continuous loading temp of conductor 90°C
(iii) Clipped direct, one 3 or 4 core cables, 3 phase a.c.
Categories
•
CU/XLPE/PVC
•
CU/XLPE/SWA PVC
•
AL/XLPE/PVC
•
AL/XLPE/SCT/PE
Convertion Table
•
ARMOURED CABLE
•
NON-ARMOURED Cable