The continous current carrying capacities are based on the following condition : (i) Ambient temp 30°C
(ii) Max. continuous loading temp of conductor 90°C
(iii) Clipped direct, one 3 or 4 core cables, 3 phase a.c.
CU and AL Conversion Table for XLPE/PVC Cables
Nominal cross-sectional area
For CU
Cu conductor current rating (Amp)
Votage drop CU conductor
(V/A/km)
Votage drop AL conductor
(V/A/km)
Equivalent current rating of AL conductor (Amp)
Nominal cross-sectional area
For AL
10mm²
74
4.0
4.2
80
16mm²
16mm²
99
2.5
2.7
97
25mm²
25mm²
130
1.60
1.45
149
50mm²
35mm²
161
1.15
0.98
189
70mm²
50mm²
209
0.87
0.73
234
95mm²
70mm²
268
0.61
0.59
273
120mm²
95mm²
326
0.45
0.47
314
150mm²
120mm²
379
0.37
0.39
366
185mm²
150mm²
436
0.31
0.32
438
240mm²
185mm²
500
0.26
0.27
507
300mm²
240mm²
590
0.22
0.23
594
400mm²
300mm²
681
0.195
0.20
692
500mm²
400mm²
793
0.175
0.185
791
630mm²
500mm²
904
0.160
0.170
911
800mm
630mm²
1033
0.150
0.160
1072
1000mm
800mm²
1179
0.145
0.150
1217
1200mm
(A) CU and CL Conversion Table For 2 Core CU/XLPE/SWA/PVC 1KV and AL/XLPE/SCT/PE 1KV Cables
Nominal cross-sectional area
For CU
Cu conductor current rating (Amp)
Votage drop CU conductor
(V/A/km)
Votage drop AL conductor
(V/A/km)
Equivalent current rating of AL conductor (Amp)
Nominal cross-sectional area
For AL
10mm²
85
4.7
4.8
84
16mm²
16mm²
110
2.9
2.2
126
35mm²
25mm²
146
1.9
1.65
154
50mm²
35mm²
180
1.35
1.15
198
70mm²
50mm²
219
1.00
0.84
241
95mm²
70mm²
279
0.69
0.67
281
120mm²
95mm²
338
0.52
0.56
325
150mm²
120mm²
392
0.42
0.45
371
185mm²
150mm²
451
0.35
0.36
436
240mm²
185mm²
515
0.29
0.31
500
300mm²
240mm²
607
0.24
0.26
566
400mm²
(B) CU and AL Converstion Table for 4 Core CU/XLPE/SWA/PVC 1KV and AL/XLPE/SCT/PE 1KV Cables